Duct fans for round systems with a capacity of up to 5260 m3 / h
The VKM and VKMS series are designed for supply or exhaust systems of individual rooms, individual buildings, collective residence and public utilities. For ventilation with increased requirements regarding noise level, Q or E variants are recommended.
VKMS fans differ from similar VKM models with engine power.
The fans use single-phase motors with ball bearings, with an external rotor and curved blades to the rear. The motors have built-in protection with an automatic restart to prevent them from overheating.
The capacity regulation can be performed smoothly (thyristor controller) or in a step-wise manner (transformer regulator). It is possible to connect several units to one controller, provided that the available power and operating current will not exceed the nominal parameters of the regulator.
The fans can be mounted at any angle to the ground, wall or ceiling (brackets included).
Engine safety class: IP X4
VKMS – engine with increased power
VKM E – economical fan operation
VKM Q – engine with reduced power

| VKM 100 Q | VKM 100 | VKM 125 Q | VKM 125 | VKM 150 | VKM 160 | VKM 200 | VKMS 200 | |
| Voltage (V) | 230 | 230 | 230 | 230 | 230 | 230 | 230 | 230 |
| Power (W) | 60 | 73 | 60 | 75 | 98 | 98 | 154 | 193 |
| Power consumption (A) | 0,37 | 0,32 | 0,37 | 0,33 | 0,43 | 0,43 | 0,67 | 0,84 |
| Efficiency (m3/h) | 210 | 270 | 255 | 355 | 555 | 555 | 950 | 1100 |
| Speed (min-1) | 2620 | 2830 | 2535 | 2800 | 2705 | 2660 | 2375 | 2780 |
| Loudness [dB(A)/3 m] |
36 | 47 | 36 | 47 | 47 | 47 | 48 | 51 |
| Max. working temp.(°C) | 30 | 30 | 30 | 30 | 30 | 30 | 25 | 20 |
| Protection class | IP X4 | IP X4 | IP X4 | IP X4 | IP X4 | IP X4 | IP X4 | IP X4 |
| VKM 250 Q | VKM 250 | VKM 315 | VKMS 315 | VKM 355 Q | VKM 400 | VKM 450 | |
| Voltage (V) | 230 | 230 | 230 | 230 | 230 | 230 | 230 |
| Power (W) | 158 | 194 | 171 | 296 | 233 | 460 | 665 |
| Power consumption (A) | 0,69 | 0,85 | 0,77 | 1,34 | 1,06 | 2,23 | 2,89 |
| Efficiency (m3/h) | 1190 | 1310 | 1400 | 1880 | 2210 | 3050 | 5260 |
| Speed (min-1) | 2315 | 2790 | 2600 | 2720 | 1375 | 1370 | 1265 |
| Loudness[dB(A)/3 m] | 52 | 52 | 52 | 54 | 58 | 61 | 65 |
| Max. working temp. (°C) | 25 | 25 | 25 | 20 | 20 | 40 | 30 |
| Protection class | IP X4 | IP X4 | IP X4 | IP X4 | IP X4 | IP X4 | IP X4 |
| Type | Sizes (mm) | Weight (kg) | |||||||
| ØD | ØD1 | B | B1 | L | L1 | L2 | L3 | ||
| VKM 100 E | 100 | 204 | – | – | 195 | 20 | 20 | 258 | 3,9 |
| VKM 100 Q | 98 | 254 | 298 | 258 | 205 | 20 | 25 | 30 | 4,2 |
| VKM 100 | 98 | 254 | 298 | 258 | 205 | 20 | 25 | 30 | 4,4 |
| VKM 125 E | 125 | 204 | – | – | 195 | 20 | 20 | 258 | 3,9 |
| VKM 125 Q | 123 | 254 | 298 | 258 | 205 | 20 | 25 | 30 | 4,1 |
| VKM 125 | 123 | 254 | 298 | 258 | 205 | 20 | 25 | 30 | 4,3 |
| VKM 150 Q | 149 | 304 | 349 | 309 | 200 | 20 | 25 | 30 | 5,4 |
| VKM 150 | 149 | 304 | 349 | 309 | 220 | 25 | 25 | 30 | 5,4 |
| VKMS 150 | 149 | 340 | 386 | 346 | 226 | 20 | 20 | 40 | 5,7 |
| VKM 160 Q | 159 | 304 | 349 | 309 | 200 | 20 | 25 | 30 | 5,4 |
| VKM 160 | 159 | 304 | 357 | 317 | 220 | 25 | 25 | 30 | 5,6 |
| VKMS 160 | 159 | 340 | 386 | 346 | 226 | 20 | 20 | 40 | 5,7 |
| VKM 200 | 198 | 344 | 390 | 350 | 240 | 25 | 29 | 40 | 6,6 |
| VKMS 200 | 198 | 344 | 390 | 350 | 250 | 25 | 29 | 40 | 6,7 |
| VKM 250 Q | 248 | 344 | 390 | 350 | 249 | 25 | 31 | 40 | 7,1 |
| VKM 250 | 248 | 344 | 390 | 350 | 249 | 25 | 31 | 40 | 7,3 |
| VKM 315 | 314 | 404 | 454 | 414 | 260 | 25 | 40 | 40 | 8,1 |
| VKMS 315 | 314 | 404 | 454 | 414 | 288 | 25 | 40 | 40 | 8,2 |
| VKM 355 Q | 353 | 460 | 522 | 522 | 506 | 60 | 60 | 70 | 12,8 |
| VKM 400 | 398 | 570 | 663 | 634 | 570 | 60 | 60 | 70 | 20 |
| VKM 450 | 448 | 608 | 700 | 670 | 644 | 60 | 60 | 80 | 30 |